Solutions

《Mantunsci S3 Series Smart Safety Distribution and Metering Management System Scheme in Dormitory》

Views:14    Time:2019-05-20

1. Summary of the scheme

This scheme adopts the intelligent power management system and the Mantunsci S3 series of smart miniature circuit breakers, which are used as safety protection and measurement for each dormitory. It can be installed directly on the rails of low-voltage power distribution cabinets in the floor distribution room, or in the lighting electrical boxes in the dormitory.

 

2. System configuration and product selection

a. In the low-voltage distribution room on the floor, each rental house can be equipped with a wisdom micro-break with leakage protection and Mantunsci S3-ZNC63, 220VAC, 32A, 2P (each switch actually takes 3P position on the electrical box rail);

Each 8 room in the distribution room is equipped with a S3-P25 power module (each occupying 2P position, plus one for each additional 8);

One S3-T30 communication module is equipped per power distribution room (1P location, plus one if more than 24 rooms and add a network cable).

Number

Name

Model

Quantity

Annex

01

Single-phase, 2P, smart micro-break with leakage protection

S3-ZNC32

N=Number of dormitories

Self-inspection with leakage protection function.

Rated current:32A

Breaking capacity:6KA

02

Power supply and surge protection module

S3-P25

1

Plus 1 for every 8 rooms

03

Communication module

S3-T30

1

Plus 1 for every 24 rooms

 

b. Install a smart micro-break with leakage protection and Mantunsci S3-ZNC32, 220VAC, 32A, 2P in each dormitory. (Each switch actually takes 3P position on the electrical box rail) and configure an S3-P25 power module and a S3-T30 communication module.

Number

Name

Model

Quantity

Annex

01

Single-phase, 2P, smart micro-break with leakage protection

S3-ZNC32

1

Self-inspection with leakage protection function.

Rated current:32A

Breaking capacity:6KA

02

Power supply and surge protection module

S3-P25

1

DC12V\2.5A

03

Communication module

S3-T30

1

TCP protocol with network port

 

Installation requirements:

1. When designing, you should leave the RJ45 network cable connector or socket in the low-voltage power distribution cabinet of the power distribution room, which is located near the installation position of the communication module T30. If the environment is not convenient for wiring, you can also choose the wireless WIFI working mode as long as the full coverage of WIFI signal;

2. When designing, it is recommended to leave more 1P space for the low-voltage distribution cabinet rail to facilitate the installation of intelligent micro-break and related accessories;

3. It can remotely control the use of electrical appliances, overload protection, short circuit protection, leakage protection, and meter power consumption.

 


Previous:《Mantunsci S3 Series Smart Safety Distribution and Metering Management System Scheme in Hotel Apartment》 Next:《Mantunsci S3 Series Rental Housing Smart Safety Distribution and Metering Management System Schemes》